0154ESERIES

Brooks Instrument 0154E Series Four-Channel Mass Flow Readout and Control Unit

About this part

The Brooks Instrument 0154E Series is a microprocessor-based, four-channel secondary-electronics platform that powers, displays, and controls compatible mass-flow, pressure, and Quantim devices. It supports independent or master/slave blending operation, programmable engineering-unit or percent-of-full-scale readout, valve override, local or remote control, analog process signals, and RS-232 communications. Housing, power-supply, and analog-I/O selections depend on the complete configured order code

Configurations vary. Verify the exact unit before choosing a replacement.

No archived photo available

Key Facts

ManufacturerBrooks Instrument
Part number0154ESERIES
Product familyConfiguration-specific
Device typeController
Configuration statusConfiguration varies
Application classIndustrial automation and process equipment
CategoryFlow Control

Specifications

Identification
Manufacturer model0154E Series; later manufacturer literature identifies the platform as Model 0154
Function
Number of channels4 independent or master/slave channels
Supported instrumentsCompatible Brooks gas/liquid thermal mass-flow meters and controllers, pressure meters and controllers, and Quantim Coriolis devices
Readout valuesFlow, pressure, density, or temperature; programmable as engineering units or percent of full scale per channel
Control functionsSetpoint control, blending, valve override, local/remote selection, totalization, and high/low alarms
Display
DisplayBacklit 4 × 20-character display for Model 0154
Controls
Operator interfaceMembrane keys for channel selection, setpoint, blending, valve override, local/remote control, and menu functions
Power
AC input ratingDesign specification: 90–260 VAC, 50/60 Hz, 70 W maximum; certification and observed nameplate material also show 100–240 VAC, 50/60 Hz, 100 W, so the configured-unit nameplate governs
Instrument power output options+15 VDC at 2.9 A and −15 VDC at 1.4 A maximum, or 24 VDC at 2.5 A maximum
Signals
Analog input and output ranges0–5 V, 1–5 V, 0–20 mA, or 4–20 mA; the manual also documents optional-board support for 0–10 V
Voltage-output load1 kΩ minimum impedance
Current-output load750 Ω maximum impedance
Connections
Channel connectorsFour 15-pin D-sub connectors for connected flow or pressure instruments
Remote process I/OOne 25-pin D-sub connector carrying flow outputs and remote setpoint inputs for up to four channels
External valve overrideOne 15-pin D-sub connector
Communications
Serial interfaceStandard 9-pin RS-232 connection for PC control, readout, and data exchange
Construction
Housing materialAnodized aluminum with steel covers
Mounting
Housing optionsHalf-width 19-inch rack cassette, rack mount, panel mount, or table-top housing; optional table-top handle
Dimensions
Rack cassette130 × 220 × 230 mm (5.1 × 8.7 × 9.1 in), height × width × depth
Panel cutout241 × 142 mm (9.5 × 5.6 in)
Environment
Ambient operating temperature0–50 °C (32–122 °F)
Protection
Mains fusesTwo 5 × 20 mm, 2 A time-delay fuses; replacement voltage rating must suit the applied mains supply
Compliance
CertificationCE identified in the manufacturer design specification

Configuration boundary

0154ESERIES is an archive-normalized series identifier rather than a complete Brooks order code. The complete code and equipment nameplate are required to establish the installed housing, ±15 VDC versus 24 VDC instrument supply, analog signal range, mains rating, connector arrangement, and optional I/O hardware.

Channel connector pinout

The manufacturer manual assigns the following functions to each 15-pin channel connector. Power pins depend on whether the unit was built for ±15 VDC or 24 VDC operation.

PinDirectionFunction
1Output+15 VDC or +24 VDC
2InputFlow-current signal
3OutputCurrent setpoint
4—Not connected
5OutputVoltage setpoint
6—Setpoint ground
7OutputValve override
8—Flow-signal ground
9—Reserved
10InputFlow-voltage signal
11—Not connected
12—Power ground
13Output+15 VDC or +24 VDC
14Output−15 VDC on ±15 V units; not connected on 24 V units
15—Not connected

Successor and retrofit relationship

Brooks identifies the 0152/0154 secondary-electronics products as discontinued and replaced by the 0250 Series. The four-channel Model 0254 has a documented retrofit arrangement for the table-top enclosure formerly used by Models 0152/0154.

Successor familyBrooks 0250 Series
Four-channel successorModel 0254
Mechanical retrofitThe Model 0254 rack-mount kit and power-supply hardware can be installed in a Model 0152/0154 table-top enclosure.
Replacement boundaryRetrofit enclosure compatibility does not establish drop-in electrical compatibility; signal type, power option, cables, and connected-device requirements must be checked.

Documentation Downloads

Local PDF copies

Part Photos

0 images

Historical archive images for identification, labels, connectors, and condition reference, not current inventory.

Historical Listings & Prices

Historical listing data, not a current offer
Archive records1Tracked historical listing records
Historical median price$201.74Based on archived listing records
Recorded price range$201.74 - $201.74Low to high recorded listing price
Local documents3PDF copies available from Sonisys